Overload relay working principle and features of thermal motor overload
Thermal overload relays play a very important for protection of motors
and generators both. It should be very interesting to know how an
Thermal overload works as all over load relays have same working
principle.
Thermal motor overload protection relays feature bi-metal strips jointly
with a trip mechanism in a casing made of insulating material. Whenever
there is overload The motor current heats the bi-metal strips, making
them bend and activating the trip mechanism after a particular interval
which is based on the current- setting.
The release mechanism actuates an auxiliary switch that breaks the motor
contactor's coil circuit as shown in circuit diagrams below. A changing
position indicator signals the condition "tripped".
Above diagrams shows where overload is connected in motor circuit. You
may see that in Control circuit overload relay comes first in line but
in power circuit it comes at last in line.
Question arises why this is done??
This all done because to protect motor circuit as if any problem
occurred in motor then instantly motor overload relay get tripped
protecting other circuit from effects of motor faults.
Principle of operation of a three terminal delayed bimetal motor protection relay with temperature compensation
Fig. above shows the circuit of overload relay , various components are discussed below:-
A = heated bimetal strips
B = Trip slide
C = Trip lever
D = Contact lever
E = Reparation bimetal strip
The bimetal strips may be warmed directly or indirectly. In the first
case, the current flows directly through the bimetal, in the second
through an insulated heating.
The insulating material causes some delay of the heat flow so that the
inertia of thermal relays that are heated is greater than with their
right heated counterparts. Often both principles are joined.
For motor rated currents over approx. 100 A, the motor current is
conducted via current transformers. The current transformer's secondary
current subsequently heats the thermal overload relay.
This means that the dissipated power is reduced and, on the other, that the short-circuit withstand ability is raised.
The tripping current of bimetal relays can be set on a current scale -
by displacement of the trip mechanism relative - so that the protection
characteristic can be matched to the secure item in the key area of
continuous responsibility.
The uncomplicated, economic layout can just approximate the transient thermal characteristic of the motor.
The thermal motor protection relay provides perfect protection for the
motor, for beginning with following constant obligation. With frequent
startups in intermittent operation the bimetal strips compared to the
motor's significantly lower heating time constant leads to early
tripping in which the thermal capacity of the motor is not used.
The cooling time constant of thermal relays is not longer than that of
normal motors. This additionally leads to an increasing difference
between the actual temperature and that simulated by the thermal relay
in intermittent procedure.
Therefore, the protection of motors in irregular operation is not sufficient.
Temperature compensation
The principle of operation of thermal motor protection relays is centered on temperature rise.
Therefore the ambient temperature of the unit changes the tripping
specifications. As the setup site and consequently the ambient
temperature of the motor to be shielded usually is different from that
of the protective device it is an industry standard the tripping
characteris-tic of a bimetal relay is temperature-compensated, i.e.
mostly independent of its ambient temperature.
Tripping tolerances for temperature -compensated overload relays
Figure above shows Tripping tolerances for temperature-compensated overload relays for motor protection under IEC 60947-4-1
I = Overload as a multiple of the set current
delta = Ambient temperature
Limit values-
That is attained with a compensation bimetal strip that makes the relative position of the trip mechanism independent.
Sensitivity to period failure
The tripping feature of three-pole motor protection relays applies
subject to the state that all three bimetal strips are loaded with
exactly the same current at exactly the same time.
If, when one pole conductor is interrupted, only two bimetal strips are
not cool then the force needed to actuate the trip mechanism must be
alone produced by both of these strips. This demands a higher current or
results in a more tripping time (characteristic curve c in Figure).
Typical trip characteristics of a motor protection relay
Ie= Rated current set on the scale
T = Tripping time
From a cold state:
a = 3-pole load, symmetrical
b = 2-terminal load with differential release
c = 2-terminal load without differential release
From your warm state:
d = 3-pole load, symmetrical
As a way to also ensure the thermal overload protection of the motor in
the instances of supply asymmetry and decline of a stage, high quality
motor protection relays have mechanisms with phase failure sensitivity
Thermal overload relays play a very important for protection of motors
and generators both. It should be very interesting to know how an
Thermal overload works as all over load relays have same working
principle.
Thermal motor overload protection relays feature bi-metal strips jointly
with a trip mechanism in a casing made of insulating material. Whenever
there is overload The motor current heats the bi-metal strips, making
them bend and activating the trip mechanism after a particular interval
which is based on the current- setting.
The release mechanism actuates an auxiliary switch that breaks the motor
contactor's coil circuit as shown in circuit diagrams below. A changing
position indicator signals the condition "tripped".
Above diagrams shows where overload is connected in motor circuit. You
may see that in Control circuit overload relay comes first in line but
in power circuit it comes at last in line.
Question arises why this is done??
This all done because to protect motor circuit as if any problem
occurred in motor then instantly motor overload relay get tripped
protecting other circuit from effects of motor faults.
Principle of operation of a three terminal delayed bimetal motor protection relay with temperature compensation
Fig. above shows the circuit of overload relay , various components are discussed below:-
A = heated bimetal strips
B = Trip slide
C = Trip lever
D = Contact lever
E = Reparation bimetal strip
The bimetal strips may be warmed directly or indirectly. In the first
case, the current flows directly through the bimetal, in the second
through an insulated heating.
The insulating material causes some delay of the heat flow so that the
inertia of thermal relays that are heated is greater than with their
right heated counterparts. Often both principles are joined.
For motor rated currents over approx. 100 A, the motor current is
conducted via current transformers. The current transformer's secondary
current subsequently heats the thermal overload relay.
This means that the dissipated power is reduced and, on the other, that the short-circuit withstand ability is raised.
The tripping current of bimetal relays can be set on a current scale -
by displacement of the trip mechanism relative - so that the protection
characteristic can be matched to the secure item in the key area of
continuous responsibility.
The uncomplicated, economic layout can just approximate the transient thermal characteristic of the motor.
The thermal motor protection relay provides perfect protection for the
motor, for beginning with following constant obligation. With frequent
startups in intermittent operation the bimetal strips compared to the
motor's significantly lower heating time constant leads to early
tripping in which the thermal capacity of the motor is not used.
The cooling time constant of thermal relays is not longer than that of
normal motors. This additionally leads to an increasing difference
between the actual temperature and that simulated by the thermal relay
in intermittent procedure.
Therefore, the protection of motors in irregular operation is not sufficient.
Temperature compensation
The principle of operation of thermal motor protection relays is centered on temperature rise.
Therefore the ambient temperature of the unit changes the tripping
specifications. As the setup site and consequently the ambient
temperature of the motor to be shielded usually is different from that
of the protective device it is an industry standard the tripping
characteris-tic of a bimetal relay is temperature-compensated, i.e.
mostly independent of its ambient temperature.
Tripping tolerances for temperature -compensated overload relays
Figure above shows Tripping tolerances for temperature-compensated overload relays for motor protection under IEC 60947-4-1
I = Overload as a multiple of the set current
delta = Ambient temperature
Limit values-
That is attained with a compensation bimetal strip that makes the relative position of the trip mechanism independent.
Sensitivity to period failure
The tripping feature of three-pole motor protection relays applies
subject to the state that all three bimetal strips are loaded with
exactly the same current at exactly the same time.
If, when one pole conductor is interrupted, only two bimetal strips are
not cool then the force needed to actuate the trip mechanism must be
alone produced by both of these strips. This demands a higher current or
results in a more tripping time (characteristic curve c in Figure).
Typical trip characteristics of a motor protection relay
Ie= Rated current set on the scale
T = Tripping time
From a cold state:
a = 3-pole load, symmetrical
b = 2-terminal load with differential release
c = 2-terminal load without differential release
From your warm state:
d = 3-pole load, symmetrical
As a way to also ensure the thermal overload protection of the motor in
the instances of supply asymmetry and decline of a stage, high quality
motor protection relays have mechanisms with phase failure sensitivity
No comments